Argus Switched Mode Battery Charger 010-523-B2
MANUAL ADDENDUM Unit Description: Argus Switched Mode Battery Reverting Charger Manual P/N: 010-519-C0 Applies to Manual Revision: A # Date Page#
# Date Page# Line# Correction to be implemented 4 5 11 Insert Figure (below): Figure 3–Front panel of 24V 10A Battery Reverting Charger (010
IMPORTANT SAFETY INSTRUCTIONSSAVE THESE INSTRUCTIONS - This manual contains important safety and operatinginstructions for the Argus battery charger:1
INSTALLATION AND OPERATOR'S MANUAL FOR ARGUS BATTERY CHARGERTable of Contents1.0 WARRANTY2.0 DOCUMENTATION - PART NUMBER INFORMATION ...
5.0 OPERATION ...135.
010-519-C0 Rev. A Page 1 of 15 ARGUS TECHNOLOGIES2.0 DOCUMENTATION - PART NUMBER INFORMATION2.1 IntroductionPlease read this manual thoroughly prior t
3.0 GENERAL3.1 ScopeThis instruction manual covers the installation, and operation of Argus Technologies' BatteryCharger.3.2 IntroductionThe Argu
3.3.1.3 Automatically disconnecting the battery from the load:When a transfer occurs the batteries will be connected to the load for a minimum of 2 se
AC power must be restored and the battery voltage must rise to 12.0 V (24.0 V) before the LVDcondition is cleared.The low voltage disconnect will not
3.3.6 Reverse Battery Protection:In the event the battery is installed backwards fuse(s) F4 (F200) in the charger will blow. Ensurefuses are replaced
Argus Technologies Ltd. Visit www.argus.ca Burnaby, British Columbia. Telephone: 604 436 5900 Fax: 604 436 1233 Argus Technologies reserves the
3.4.7 Voltage Down and Voltage Up Pushbuttons (12V and 24V sections):These momentary push button switches will increment and decrement the output volt
4.0 INSTALLATION INSTRUCTIONS4.1 Tools RequiredEXAMPLE:- Philips screw driver, #2 (Tip Size 3/16")- Philips screw driver, #3 (Tip Size 1/4")
WARNING: JUMPERS FOR BOTH TERMINAL BLOCKS MUST BE SETTO THE PROPER INPUT VOLTAGE SETTING BEFORE AC IS APPLIED.Failure to do so may result in damage to
4.4.3 Battery ConnectionRemove the battery fuse(s) before connecting or disconnecting the battery cables from the batteryand/or charger.1/4” - 20 stud
ARGUS TECHNOLOGIES 010-519-C0 Rev. A Page 10 of 15
4.4.5 Alarm Contacts Connections4.4.5.1 On Battery AlarmTerminal block accepts #18 to #24 AWG wire and provides three terminals (Form C contacts) whic
The probe(s) can also be connected directly to a battery terminal. When this is done both probesmust be connected to the same terminal. The probe is e
5.0 OPERATION5.1 StartupEnsure all power and alarm connections are secure and the AC input voltage selection jumpers areset correctly (see AC Voltage
6.0 SETTINGS/ADJUSTMENTS6.1 Factory Settings12V Output: 13.7VDC24V Output: 27.4VDCAC input voltage selection jumpers set for 120VAC.6.2 Adjustments6.2
This page intentionally left blank.
Argus Technologies Ltd. 010-523-B2 Rev C WC Printed in Canada. © 2005 Argus Technologies Ltd. ARGUS is a registered trademark of Argus Technologi
Technical SupportTechnical support staff are available for answering general questions related to installation, operation and maintenance of Argus pro
SPECIFICATIONS FOR ARGUS TECHNOLOGIES BATTERY CHARGER, 24V/10ABattery Output:Voltage: Float: 24-30 VDCEqualize: Float + 2.0 VCurrent: 10 ADCPower: 250
Input:Voltage: 85-140 VAC (47-63 Hz)180-264 VAC (47-63 Hz)Current: 3.7 Amps (120 VAC nominal) @ 250 Watts output1.9 Amps (240 VAC nominal) @ 250 Watts
Environmental:Cooling: Natural ConvectionTemperature: -30ºC to +60ºC (-22ºF to +140ºF) (operating)Humidity: 0-95% Relative Humidity @ +50ºC (non-conde
Warranty PolicyArgus Technologies Ltd. warrants all equipment manufactured by it to be free from defects in parts and labor, excluding third party OEM
What are the CSA and NRTL?CSA (Canadian Standards Association also known as CSA International) was established in 1919 as an independent testing labor
MANUAL ADDENDUMAuthorized by: FORM 954-010-10 010519c1.docMANUAL ADDENDUMUnit Description: Argus Switch Mode Battery ChargerManual P/N: 010-519-C0 App